Technical Data
Sn [kVA] |
|
Pn [kW] |
|
Input / output 3/1 |
|
Input / output 3/3 |
|
Parallel configuration |
up to 6 units |
Input
Rated voltage |
3ph + N: 400 V (can be configured 380/415 V) |
Voltage tolerance |
240 V to 480 V |
Rated frequency |
50/60 Hz ± 10% |
Output
Power factor |
0.9 (according to IEC/EN 62040-3) |
Rated voltage |
1ph + N: 230 V (can be configured 220/240 V)
3ph + N: 400 V (can be configured 380/415 V)
|
Rated frequency |
50/60 Hz |
Efficiency (TÜV SÜD verified)
Double conversion VFI mode |
up to 95% |
Eco mode |
up to 99% |
Battery
Technologies |
VRLA, NiCd |
Battery type |
normal life |
Configuration |
External batteries |
Environment
Operating ambient temperature |
up to +40 °C(2) |
UPS cabinet
Dimensions W x D x H |
442 x 830 x 305 mm |
Weight |
79 kg max(1) |
Display |
3.5” |
Degree of protection |
IP20 (IP21 on demand) |
Colours |
metallised grey E150HVR |
Standards
Safety |
IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2 |
EMC |
IEC/EN 62040-2, AS 62040.2 |
Performance |
IEC/EN 62040-3, AS 62040.3 |
Environmental |
full compliance with the RoHS EU directive |
Product declaration |
CE, RCM (E2376) |
(1) According to the model.
(2) Conditions apply.
Download Brochure