UPS and internal batteries
Cabinet type S height 800 mm
Cabinet type M height 1000 mm
Cabinet type T height 1400 mm
Technical data
Sn [kVA] |
|
Pn [kW] |
|
Input / output 3/1 |
|
Input / output 3/3 |
|
Parallel configuration |
1+1(1) |
Input
Rated voltage |
400 V 3ph + N |
Voltage tolerances |
240 V to 480 V(2) |
Rated frequency |
50/60 Hz ± 10% |
Power factor / THDI |
0.99 / < 3% |
Output
Rated voltage |
1ph + N: 230 V (can be configured 220/240 V)
3ph + N: 400 V (can be configured 380/415 V) |
Voltage tolerance |
static load ±1% dynamic load in accordance with VFI-SS-111 |
Rated frequency |
50/60 Hz |
Frequency tolerance |
± 2% (configurable from 1% to 8%) |
Overload |
125% for 10 minutes, 150% for 1 minute |
Crest factor |
3:1 |
Bypass
Rated voltage |
rated output voltage |
Voltage tolerance |
± 15% (configurable with from 10% to 20%) |
Rated frequency |
50/60 Hz |
Frequency tolerance |
± 2% (configurable for Genset compatibility) |
Efficiency
Online mode @ 100 % of load |
up to 94.5% |
Environment
Operating ambient temperature |
from 0 °C up to 40(2) °C (from 15 °C to 25 °C for maximum battery life) |
Relative humidity |
0% - 95% without condensation |
Maximum altitude |
1000 m without derating (max. 3000 m) |
Acoustic level at 1 m (ISO 3746) |
|
UPS cabinet
Dimensions W x D x H |
444 x 795 x 800 / 1000 / 1400 mm |
444 x 795 x 1400 mm |
|
Weight(3) |
105kg |
110kg |
135kg |
152kg |
180kg |
200kg |
|
Degree of protection |
IP20 |
Colours |
RAL 7012 |
Standards
Safety |
IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2 |
EMC |
IEC/EN 62040-2, AS 62040.2 |
Performance |
IEC/EN 62040-3, AS 62040.3 |
Product declaration |
CE, RCM (E2376) |
(1) The standard model is prepared for a 1+1 redundant system. Upon request, it is possible to have connected up to 6 modules in a parallel system.
(2) Conditions apply.
(3) Without batteries.
Download Brochure