Redundant design for power availability and site maintainability
Static Transfer System from 200 to 1600 A

Advantages
STATYS provides
- High reliability - internal redundant design. Flexibility and adaptability to various types of applications.
- Compact design: saves up to 40% of valuable space.
- Operational security and ease of use Remote data access in real time and from any location.
- Full support and service.
High availability
- Complete separation of both sources and the related distribution systems.
- Dual source redundancy supplies the load choosing the best source quality ensuring continuity
- No-break transfer of the loads.
- Distributed STS for load separation avoiding mutual disturbances.
- Full internal redundant design and failure management.
- Separation of main functions to prevent internal fault propagation.
- Neutral loss detection on both sources.
High flexibility
- Suitable for all types of:
- applications and power supply systems,
- electrical environment conditions,
- load to protect. - Easy installation:
- for existing or new electrical plants,
- compact units,
- front access. - Available with or without neutral connection and with or without neutral pole switching.
Technical Data
Size(A) |
|
Electrical specifications
Voltage | 208 - 220 / 380 - 415 / 440 V (±10%) |
Number of phases | 3ph+N or 3ph (+ PE) |
Frequency | 50 Hz or 60 Hz (±5 Hz (configurable)) |
Number of poles switching | 3 or 4-pole switching |
Neutral system | Compatible with all earthing systems |
Maintenance bypass | Interlocked and secured |
Overloads | 150% for 2 minutes - 110% for 60 minutes |
Efficiency | 99% |
Admissible power factor | No restrictions |
Environment
Operating ambient temperature | 0 - 40 °C | ||
Relative humidity | 95% | ||
Maximum altitude | 1000 m a.s.l. without derating | ||
Cooling | Forced ventilation | ||
Acoustic level at 1 m (ISO 3746) |
|
Mechanical specifications
Dimensions W x D x H |
| |||||
Weight |
| |||||
Degree of protection | IP20 |
Standards
Performance and safety | IEC 62310, IEC 60529, AS 62310, AS 60529 |
EMC | C2 category (IEC 62310-2, AS 62310.2) |
Protection class | CB or PC class |
Product declaration | CE, RCM (E2376) |
(1) Depth does not include handles (+40 mm).