The ZENER uZen 101 range single phase input-single phase output is a double conversion Online UPS with Active Input Power Factor Correction up to 0.99 and with less than 10% input current harmonics.
Apart from providing backup on power failure it is also a perfect power conditioner providing international levels of voltage and frequency stabilization.
Technical Data
| CAPACITY | 1 - 7.5kVA |
| DC BUS | 36V /48V /72V /96V /120V / 192V |
INPUT
| Mains Voltage | 230VAC, 1PH |
| Mains Range | 170V - 270V |
| Mains Frequency | 50 Hz ± 10% |
BATTERY
| Charger Type | CC / CV |
| Charger Current limit | Adjustable, normally set at 10% of Ah capacity |
INVERTER
| Technology | High Frequency PWM |
| Nominal Output Voltage | 230V / 240AC ( Adjustible) |
| Regulation | ±1% |
| Waveform | Sinusoidal |
| Frequency | 50 Hz ± 0.25Hz |
| Crest Factor | 3:1 |
| Over Load Capacity | 125% - 1 min & 150% - 10 Secs |
| Power Factor | 0.8 lag to unity |
| Power Device | IGBT |
| Transient Response | Output remains within ± 5% & recover to normal with in 20msec |
| Static Switch | Optional |
| Super Bypass Switch | Available |
PROTECTIONS
| Input | MCBs at Input & Output, MOVs, Snubber Circuits, Fastblow SemiConductor Fuse and Soft start, Single Phase Protection |
| Inverter Over Voltage / Under Voltage | 255VAC / 185V |
| General Protections | Semiconductor Fuse, MCB, EMI Filters, Over Temperature, Mains High Voltage & Short Circuit |
| Low Battery Trip | Yes |
| Enclosure Protection | IP - 20 |
GENERAL
| Efficiency | > 90% |
| Isolation | Online UPS with Galvanic Isolation for comprehensive power protection |
| LED Indications | Mains ON, Charger ON, Inverter ON, Battery Low, Over Load, Charger Trip, Inverter Trip, Over Temp, On Bypass |
| LCD Display | Mains Voltage, Output Voltage, Load Current, Battery Voltage, Output Frequency, Temperature |
| Audible Alarms | Input Low / Fail, Over Load, Battery Low, Over Temp, Inverter Trip |
| Cooling | Forced Air |
ENVIRONMENT
| Ambient Temperature | 0 - 45ºC |
| Noise Level | <60 db @ 1.5 meter |
| Relative Humidity | 0 - 90% Non condensing |
| Mobility | Castor Wheels |