Problems with power quality and continuity can be sudden and very frequent. ITYS E from 1 to 10 kVA ensures high availability, operational efficiency and total electrical protection for your business against any electrical disturbance and fault.
Features
- True online double conversion technology (VFI) assures high availability and total load protection
- Constant output voltage and frequency regulation makes ITYS E compatible with different applications, operating environments and generator sets
- Automatic bypass supplies the loads in the event of overloads or faults
- Compact tower UPS system saves space in the operating environment
- No particular configuration on first startup
- Easy connections via IEC 320 sockets or terminals
- Wide input voltage tolerance limits the switchovers to battery mode prolonging the battery life
- Manual bypass for periodic or emergency maintenance
- Standard Communication Features
- Communication Options
Technical Data
ITYS E | |||||
Sn | 1000 VA | 2000 VA | 3000 VA | 6000 VA | 10000 VA |
Pn | 800 W | 1600 W | 2400 W | 4800 W | 8000 W |
INPUT
Voltage | 230 V (1ph) 160÷300 V up to 110 V @ 60% load | ||||
Rated frequency | 50/60 Hz | ||||
Power factor | 0.99 | ||||
OUTPUT
Rated voltage | 208/220/230/240 V +/- 2% (+/- 0.05 Hz in battery mode) | ||||
Voltage tolerance | ± 1% | ||||
Rated frequency | 50/60 Hz (46÷54 Hz / 56÷64 Hz) (in battery mode 50/60 ± 0.1 Hz) | ||||
Overload | Up to 130% for 1 minute | ||||
Crest factor | 3:01 | ||||
Connections(1) | 3 x Universal | 4 x Universal + terminals | terminals |
BATTERY
Type | sealed lead-acid maintenance free - expected life 3/5 years | ||||
Back-up time @75% of rated VA load pf 0.7(2) | 8 min | 9 min | |||
Voltage(3) | 36 VDC | 96 VDC | 192 VDC | 240 VDC | |
Battery charger(3) | Setting up to 6 A |
COMMUNICATION
Interfaces | RS232 - USB | ||||
Network adapter | SNMP optional card | ||||
Local communiaction software | LOCAL VIEW |
EFFICIENCY
Online mode | up to 90% |
ENVIRONMENT
Ambient temperature | 0 to 40°C (15 to 25 °C for maximum battery life) | ||||
Relative humidity | 0 to 95% without condensation | ||||
Maximum altitude | < 55 dBA | < 65 dBA |
UPS CABINET
Dimensions(2) W x D x H | 145 x 285 x 220 mm | 145 x 400 x 220 mm | 190 x 425 x 320 mm | 190 x 370 x 640 mm | 190 x 450 x 640 mm |
Weight(2) | 10 kg | 17 kg | 28 kg | 60 kg | 75 kg |
Weight(3) | 5 kg | 7 kg | 8 kg | 21 kg | 23 kg |
Dimensions(3) W x D x H | 145 x 285 x 220 mm | 145 x 400 x 220 mm | 145 x 400 x 220 mm | 190 x 370 x 320 mm | 190 x 450 x 320 mm |
Degree of protection | IP20 |
STANDARDS
Safety | - | EN 62040-1 | |||
EMC | - | EN 62040-2 |
(1) Other socket types available as option.
(2) Models with internal batteries.