Result of more than 20 years of experience in supplying modular solutions, DELPHYS XTEND GP is the latest innovative addition to the range of energy efficient UPS solutions. It combines all the benefits of the Green Power 2.0 technology and the flexibility of a modular system.
DELPHYS XTEND GP is a real hot-scalable UPS system designed to provide power scalability that can be built up with power blocks to extend the system according to the maximum power requirement.
The solution for
|
|
An innovative way to provide scalability
- Power scalability is provided by 200 kVA/kW Xmodule power blocks docked onto prewired Xbay docks
- The installation and the positioning are easy with secured operation both for operators and the application
- The load is fully protected in online double conversion mode even during system extensions or maintenance
Real hot-scalable solution
- Quick and safe scalability to meet evolving power demands
- Reliable power that can be increased when needed to rapidly meet changing capacity demands
- Easy adaptation to site evolutions and constraints
- Prewired system for additional Xmodule connection and coupling within the system
- The benefits of the real hot scalability:
- no site modifications for power upgrading,
- lower initial cost,
- reduced time and cost for power upgrading,
- reduced maintenance expenditure,
- reduced energy and cooling costs
Optimized capital employed
- Lower the initial cost by installing only the required Xmodule power blocks
- Simplifies the upstream and downstream switchboards thanks to its integrated scalability and pre-wired architecture
- Reduces time and cost for power upgrading
- Provides a cost effective maintenance thanks to system scalability
- Minimizes energy consumption with its design and technology
- Innovative battery discharge test allows significant cost savings:
- no need to rent or buy load banks,
- simplified infrastructure (no dedicated test bus bars required),
- no wasted energy (it is re-used to supply other UPS or applications),
- less time needed to perform the test (easy to programme)
Energy efficiency & adaptability
In addition of its high online efficiency, DELPHYS XTEND GP can reduce heat losses while operating under different site conditions:
- Energy Saver mode optimises the performance of a system working in double conversion during low load conditions
- Fast EcoMode increases the efficiency (up to 99%), by selecting the bypass line (VFD mode) when its quality is within the defined tolerances and stability. If the input power supply is disturbed, the load is instantaneously transferred to online double conversion (VFI mode) to ensure high power quality
A complete solution
DELPHYS XTEND GP simplifies the connection to the upstream and downstream switchboards. It eliminates installation rework costs when new capacity is required from the IT loads. Power upgrading is performed without interrupting the energy supplied to the load thanks to pre-wired platform bays that allow the power modules to be plugged or unplugged in full safety without any modification to the site’s electrical infrastructure.
Total system flexibility
DELPHYS XTEND GP is built on a flexible brick concept. It is fully adaptable to all types of infrastructure and environments. The hot scalability feature means you can scale your system according to your initial power requirements, at the same time keeping your power options open depending on future evolutions:
- the system can be set for distributed or with centralized static bypass architecture,
- common or separated rectifier and bypass mains,
- flexible battery connection with shared or distributed batteries coupling,
- IN /OUT and DC connection are available for top or bottom entry configurations,
- the system disposition can be adapted to the UPS room configuration
A manufacturer’s dedicated services
Full set of innovative services which aims at optimising your investment all along the product lifecycle while ensuring optimum availability and performance of your critical applications:
- OPEX-based costing models,
- cabling, docking and inspection service,
- preventive maintenance and original spare parts,
- 1-3-5 year contracts,
- remote monitoring (LINK-UPS),
- 24/7 hotline, accelerated response time and reduced upgrade period,
- smart battery discharge support,
- firmware consistency management
Available configurations
- With or without N+1 redundancy
- Distributed or centralised bypass
- Common or separated bypass / main input(s)
- Distributed or shared battery
- Top or Bottom entry for system connection
- Linear, “U” or “L” shaped disposition
Standard electrical features
- General input(s) and output switches
- Internal maintenance bypass
- Backfeed protection: detection circuit
- EBS (Expert Battery System) for battery management
- Battery temperature sensor
Electrical options
- Extended battery charger capability
- ACS synchronisation system
- Fast EcoMode
- Kit for 3 wires input and output (without neutral)
Standard communication features
- User-friendly multilingual interface with graphic display
- Slots for communication options
- Ethernet connection (WEB/SNMP/email)
- USB port for event log access
Communication options
- Advanced server shutdown options for stand-alone and virtual servers
- ADC interface (configurable voltage-free contacts)
- MODBUS RTU
- MODBUS TCP
- BACnet/IP interface
Remote monitoring service
- LINK-UPS, remote monitoring service that connects your UPS to your Critical Power specialist 24/7
Technical Data
System configuration | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Xmodule rated power | 200 kVA/kW | ||||||||||||
Number of Xbay docks | 4 | 5 | 6 | ||||||||||
Number of Xmodule power blocks (200 kVA/kW) | 2 | 3 | 4 | 2 | 3 | 4 | 5 | 2 | 3 | 4 | 5 | 6 | |
Power (kVA/kW) | N configuration | 400 | 600 | 800 | 400 | 600 | 800 | 1000 | 400 | 600 | 800 | 1000 | 1200 |
N+1 redundant configuration | 200 | 400 | 600 | 200 | 400 | 600 | 800 | 200 | 400 | 600 | 800 | 1000 |
Rectifier input(1) | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Voltage | 400 V 3ph (200 to 480 V(2)) | ||||||||||||
Frequency | 50 / 60 Hz | ||||||||||||
Power factor | > 0.99 | ||||||||||||
Total harmonic distortion (THDI) at full load and rated voltage | 2.5%(3) |
Inverter | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Rated output voltage | 400 V 3ph + N (380 / 415 V configurable) | ||||||||||||
Rated output frequency | 50 / 60 Hz (selectable) | ||||||||||||
Harmonic voltage distortion | ThdU ≤ 1.5 % with rated linear load |
Bypass | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Rated voltage | nominal output voltage ±15 % (settable) | ||||||||||||
Rated frequency | 50 / 60 Hz (selectable) |
Xmodule efficiency | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Online double conversion mode | up to 96 % | ||||||||||||
Fast EcoMode | up to 99 % |
(1) IGBT rectifier.
(2) Conditions apply.
(3) With input THDV < 1 %.
Dimensions
Linear integration(1) | Number of Xbay docks | W (mm) | |
---|---|---|---|
Distributed Bypass | Common or separated inputs | 4 | 4340 |
5 | 5050 | ||
6 | 5760 | ||
Centralised Bypass | Common input mains | 4 | 4840 |
5 | 5550 | ||
6 | 6260 | ||
Separated input mains | 4 | 5340 | |
5 | 6050 | ||
6 | 6760 |
(1) Please consult us for any other configuration.